Experimental prediction of total thermal resistance of a closed loop EAHE for greenhouse cooling system

Küçük Resim Yok

Tarih

2011

Dergi Başlığı

Dergi ISSN

Cilt Başlığı

Yayıncı

Pergamon-Elsevier Science Ltd

Erişim Hakkı

info:eu-repo/semantics/closedAccess

Özet

The design of an earth to air heat exchanger (EAHE) requires knowledge of its total thermal resistance (R(Tot)) for heating and cooling applications. In this research, a 47 m long horizontal, 56 cm nominal diameter U-bend buried galvanized was studied experimental EAHE used for the determination and evaluation of thermal properties of heat exchanger. This system was designed and installed in the Solar Energy Institute, Ege University, Izmir, Turkey. Based on the experimental results, generalized relationships were developed for predicting of thermal resistance of the heat exchanger. Average total heat exchanger thermal resistance was estimated to be 0.021 K-m/W as a constant value under steady state condition. (C) 2011 Elsevier Ltd. All rights reserved.

Açıklama

Anahtar Kelimeler

EAHE, Geothermal energy, Renewables

Kaynak

International Communications in Heat and Mass Transfer

WoS Q Değeri

Q1

Scopus Q Değeri

Q1

Cilt

38

Sayı

6

Künye