Effect of length-to-diameter ratio of core sample on concrete core strength - Another look

Küçük Resim Yok

Tarih

2008

Dergi Başlığı

Dergi ISSN

Cilt Başlığı

Yayıncı

Amer Soc Testing Materials

Erişim Hakkı

info:eu-repo/semantics/closedAccess

Özet

Cores with diameters of 144,94,69, and 46 mm and length-to-diameter(1/d) ratios of 0.75,1,1.25,1.5,1.75, and 2, were removed from beam specimens produced from eight different concrete mixtures. Compressive strength tests were conducted on a total of 1876 core specimens. Strength correction factors were determined for converting the strength of the cores with 1/d ratios ranging from 1.75 to 0.75 to the strength of an equivalent standard specimen with a 1/d ratio of 2. The effects of type and maximum size of aggregate and core diameter on these correction factors were examined. As it was expected, the correction factors gradually decreased with the decrease in 1/d. The effect was found to be more pronounced for cores with a smaller diameter. The results also revealed that the effects of type and maximum size of the aggregate on correction factors were not significant. The proposed strength correction factors differ only slightly from those currently recommended in ASTM C 42/C 42M-04 [1] and they are very close to those proposed by Bartlett and MacGregor cited by Arioglu et al. [2-4].

Açıklama

Anahtar Kelimeler

concrete, core strength, length-to-diameter ratio, testing, evaluation